AHU
Air handling unit: equipment that moves and conditions air, with components that depend on the specific design.
Also called: Air handling unit
In practice
The term is deliberately broad. An air handling unit is a fan section plus whatever the design needs around it — filters, a coil, dampers, humidity control, sometimes a heat recovery section. Naming something an AHU says it handles air; it does not say how the heat leaves, how capacity is controlled, or where the unit sits.
That breadth is why more specific names exist in data centers. A computer room air conditioner carries its own refrigeration; a computer room air handler uses a chilled-water coil fed from a central plant. Both are air handling units in the general sense, and the more specific name is the one that tells you about the heat path.
In larger facilities the term often refers to units serving the building rather than the data hall — ventilation for occupied areas, make-up air, or air handling for support spaces. These have their own requirements, and their relationship to the white space is usually about pressurisation, filtration and outdoor-air provision rather than about cooling the IT load.
When reading a drawing or a specification, the useful habit is to ignore the acronym and find the coil. What the coil is connected to — a refrigerant circuit, a chilled-water loop, a condenser loop — determines almost everything about how the unit behaves, what it depends on, and what fails with it.
Scope of this definition